Three-phase active harmonic rectifier (AHR) to improve utility input current THD in telecommunication power distribution system Conference Paper uri icon

abstract

  • Modern telecommunication power supply systems have several parallel-connected switch-mode rectifiers to provide -48 Vdc. A typical switch-mode rectifier configuration includes a three-phase diode rectifier followed by a dc-dc converter. Such a system draws significant harmonic currents for the utility, resulting in poor input power factor and high total harmonic distortion. In this paper, a three-phase active harmonic rectifier (AHR) scheme is proposed. In the AHR scheme, a diode rectifier module is replaced by a six-insulated-gate-bipolar-transistor pulsewidth-modulation rectifier to supply load harmonics as well as its own active power. Each dc-dc converter module is connected to a shared 48-V dc link. The AHR module together with parallel-connected switch-mode rectifiers is controlled to achieve clean input power characteristics. The VA ratings of the AHR scheme is compared with an active power filter approach. The control design is based on the synchronous reference frame approach. Analysis, simulation, and experimental results show that the AHR offers several advantages such as lower VA rating, better current control response, efficient use of the AHR dc link, small size, and stable dc-link voltage control.

name of conference

  • IEEE Transactions on Industry Applications

published proceedings

  • IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS

altmetric score

  • 9

author list (cited authors)

  • Kim, S., Todorovic, M. H., & Enjeti, P. N.

citation count

  • 27

complete list of authors

  • Kim, S||Todorovic, MH||Enjeti, PN

publication date

  • September 2003