Abolhassani, Mehdi Towliat (2005-05). Integrated electric alternators/active filters. Doctoral Dissertation. Thesis uri icon

abstract

  • In response to energy crisis and power quality concerns, three different methodologies to integrate the concept of active filtering into the alternators are proposed. Wind energy, due to its free availability and its clean and renewable character, ranks as the most promising renewable energy resource that could play a key role in solving the worldwide energy crisis. An Integrated Doubly-fed Electric Alternator/Active filter (IDEA) for wind energy conversion systems is proposed. The proposed IDEA is capable of simultaneous capturing maximum power of wind energy and improving power quality, which are achieved by canceling the most significant and troublesome harmonics of the utility grid and power factor correction and reactive power compensation in the grid. The back-to-back current regulated power converters are employed to excite the rotor of IDEA. The control strategy of rotor-side power converter is based on position sensoreless field oriented control method with higher power density. Analysis and experimental results are presented to demonstrate the effectiveness of the proposed IDEA. In next step, an integrated synchronous machine/active filter is discussed. The proposed technology is essentially a rotating synchronous machine with suitable modification to its field excitation circuit to allow dc and ac excitations. It is shown that by controlling the ac excitation, the 5th and 7th harmonics currents of the utility are compensated. The proposed method is cost effective because it can be applied to existing standby generators in commercial and industrial plants with minimal modification to the excitation circuits. To boost the gain of harmonic compensatory, an advanced electric machine is proposed. An Asymmetric Airgap Concentrated Winding Synchronous Machine (AACWSM) with ac and dc excitation was designed and employed. It is shown that the AACWSM with its unique design, in addition to power generation capability, could be used to compensate the most dominant current harmonics of the utility. The proposed AACWSM can compensate for the 5th and 7th harmonics currents in the grid by controlling the ac field excitation. In addition, the 11th and 13th harmonics currents are also significantly reduced. This system can be used at medium and low voltages for generation or motoring mode of operation.

publication date

  • May 2005