ANALYSIS OF CHOKED FLOW CONDITIONS IN A CAPILLARY TUBE-SUCTION LINE HEAT EXCHANGER.
Conference Paper
Overview
Additional Document Info
View All
Overview
abstract
Choked flow conditions at the exit of a capillary tube-suction line heat exchanger were experimentally and theoretically analyzed for refrigerant 12. The actual thermodynamic state during choked flow at the exit was calculated from experimental data and energy balances taken along incremental lengths of the capillary tube. Several existing theoretical models for two-phase choked flow were compared to each other and to the experimental data. These models can be divided into three broad categories: homogeneous equilibrium models (HEM), homogeneous frozen models, (HFM), and non-homogeneous models. Not only do the results differ greatly between categories, but in some cases they differ significantly between models within a category. The homogeneous equilibrium models showed fair agreement with the experimental data over the narrow range of conditions investigated in this study.