Modeling and Experimental Verification of a 100% Stator Ground Fault Protection Based on Adaptive Third-Harmonic Differential Voltage Scheme for Synchronous Generators
Academic Article
Overview
Research
Identity
Additional Document Info
Other
View All
Overview
abstract
2017 IEEE. In this paper, a novel adaptive stator-ground fault protection scheme based on third-harmonic differential voltages is implemented on a lab scale synchronous generator. The lab scale generator is used to emulate the fault characteristics of industrial generators along the stator windings. Simulations based on finite element analysis methods were used to design and tune the laboratory testbed. Experimental results prove the expected fault characteristics as well as fault detection capability of the adaptive stator-ground fault protection scheme.