Distribution Fault Location Using Wide-Area Voltage Magnitude Measurements Conference Paper uri icon

abstract

  • In an effort to increase situational awareness in the electric power grid, Wide-Area Measurement Systems (WAMS) are being implemented. These systems allow the capture of fastsampled voltage data such as frequency, voltage magnitude, and voltage angle measurements in a low-cost, easily deployable manner. Traditional fault location methods use both current and voltage data. Voltage monitoring devices only collect voltage data, but these sensors can collect this data anywhere along the distribution lines. An iterative simulation-based fault location method using only voltage measurements, from anywhere on the line, is proposed. This technique involves comparing a measured voltage profile of a specific fault type and phase with a calculated voltage profile obtained through simulation of such a fault occurring at various locations with a range of probable fault impedances in the system. The best match is determined using the Euclidean error norm criterion and a threshold error value. The algorithm is successfully demonstrated using a PowerWorld case study. 2013 IEEE.

name of conference

  • 2013 North American Power Symposium (NAPS)

published proceedings

  • 2013 North American Power Symposium (NAPS)

author list (cited authors)

  • Hossain, S., Zhu, H., & Overbye, T.

citation count

  • 2

complete list of authors

  • Hossain, Shamina||Zhu, Hao||Overbye, Thomas

publication date

  • January 2013