A Study of Synchronized Sampling Based Fault Location Algorithm Performance under Power Swing and Out-of-step Conditions Conference Paper uri icon

abstract

  • Relay misoperations play an important role in cascading blackouts. Power swing and out-of-step conditions caused by large disturbances in the system may result in relay misoperations. This effect is analyzed and simulated in this paper. Synchronized sampling based fault location (SSFL) algorithm was proposed as part of an advanced fault analysis tool to give precise fault information and verify relay judgments. This paper further analyzes the algorithm under power swing and out-of-step conditions and tests it by both static and dynamic scenarios generated in ATP. The test results indicate that SSFL algorithm performs better than distance relay under power swing and out-of-step conditions and can be used as a robust fault analysis tool for practical use.

name of conference

  • 2005 IEEE Russia Power Tech

published proceedings

  • 2005 IEEE Russia Power Tech

author list (cited authors)

  • Zhang, N., & Kezunovic, M.

citation count

  • 19

complete list of authors

  • Zhang, Nan||Kezunovic, Mladen

publication date

  • June 2005