Analysis of incipient behavior of multiple distribution insulators
Conference Paper
Overview
Research
Identity
Additional Document Info
Other
View All
Overview
abstract
This paper presents research characterizing the leakage (incipient behavior) of single and multiple distribution insulators through staged experiments. Four sets of field experiments were conducted over a two year period in which single and multiple insulators were artificially contaminated and energized on a lateral of a distribution system. More than 70 recordings were obtained from monitoring at the site of the insulator(s) under study and at the substation feeding the lateral. This paper focuses on the characterization of the site recordings. Individual insulator leakage currents showed an erratic behavior with bursts lasting from half a cycle to several seconds. The multiple insulators conveyed a cumulative behavior caused by individual insulators in various stages of leakage. The results are characterized graphically in the time and frequency domains.
name of conference
1999 IEEE Transmission and Distribution Conference (Cat. No. 99CH36333)